TJL, TJT, TJG series T-type clamps are suitable for branch connection of 10kV overhead insulated cables, and also suitable for T-type connection between electrical equipment in power plants and substations and overhead busbars. The insulating cover is used together with the T-shaped clip for insulating protection.
T-type clips are mainly used for overhead power lines or substations, and lead down current branches in a "T"-type manner on the main line of the busbar. There are two types of bolt type and compression type. For small cross-section wires, parallel groove wire clamps or clamping elliptical joints can also be used as T-type connections.
The meanings of the letters and numbers in the product model are:
T-T connection
Y-compression
L-bolt
The numbers indicate the nominal cross-sectional area of applicable conductors.
The holding force of the T-type clamp to the wire is not less than 10% of the calculated breaking force of the wire, but the bolt-type clamp is not less than 3% when the diameter of the wire is larger than 49mm. The DC resistance of the clip is not greater than the DC resistance of the equal-length wire, and the current-carrying temperature rise is lower than the temperature rise of the wire.
Use T-clamps with voltages of 330KV and above, with no visible corona at 1.05 times the highest operating voltage.
■Use
TJL, TJT, TJG series T-type clamps are suitable for branch connection of 10kV overhead insulated cables, and also suitable for T-type connection between electrical equipment in power plants and substations and overhead busbars. The insulating cover is used together with the T-shaped clip for insulating protection.
Insulation cover performance characteristics
◆Power frequency withstand voltage ≥18kV, no breakdown for 1 minute
◆Insulation resistance: >1.0x 1014
◆Ambient temperature: -30°C~90C
◆Weather resistance: good performance after 1008 hours of artificial weathering test
TJL aluminum T-clamp TJT copper T-clamp TJG copper-aluminum T-clamp insulation cover
■Specifications and technical parameters